Preferred CDR Draft Control System with Linear Actuator JC22-PL2-1006

Introduction | Application | Operation

The Preferred Instruments JC-22-PL2-1006 is a linear actuator with an integral microprocessor-based draft controller and a solid state draft range pressure sensor.

  •  
  • Gallery
  •  
JC22-PL2-1006
+
JC22-PL2-1006

  •  
  • Introduction
  •  
The JC22-PL2-1006 is housed in a durable metal enclosure with a removable cover.The JC22-PL2-1006 is a direct replacement for the Hays Cleveland model # 9502-1012-B-8. The JC22-PL2-1006 provides automatic modulation for any negative or positive draft application.SpecificationsWeight & Dimension: 21 lbs. 17.5” L x 7.5” W x 5.9” HPower Requirements: 120 VAC, 50/60HzMotor: 72 RPM synchronous motorSample Connection: ¼” NPT female fitting Ambient Temperature Range: 0 to 140F (-18 to 60C)
Back to top

  •  
  • Application
  •  
Travel: 6 inch linear, 60 sec. strokeThrust: 150 lbsUser Auxiliary Switch: Damper Fully Open, 16A, 250VACSet Point: Adjustable, 0 to +2.0” w.c, or 0 to -2.0” w.c. (field selectable)Dampening: Adjustable, 1.5 to 15 seconds for 90% response to a step changeDead Band: Adjustable, 0.01 to 0.08” w.c.Proportional Band: Adjustable, 0.03 to 0.2” w.c.(deviation from set point required to run at full speed)
Back to top

  •  
  • Operation
  •  

► Offers a 6-inch range of travel with a 60-second nominal stroke time. The JC22-PL2-1006’s thrust range is rated at 150 lbs with a cool-running 72 RPM synchronous motor.

►The actuator is self locking in the “last” position if there is a power loss.

► Preferred’s JC22-PL2-1006 interfaces with your burner management system:

○ The JC22-PL2-1006 is a sequencing draft controller.

○ Includes burner management interfacing relays for automated Open damper during Purge, and Closed damper after shutdown.

○ Includes an Automatic/Open selector switch. This allows the user to blow soot without interrupting the burner firing and allows the burner to fire in the “Open” damper mode under emergency conditions.

► Sensing and control functions offered via the PID controller are as follows:

○ A solid state sensor provides an accurate, low drift signal to the controller.

○ Field-adjustable Set Point for both positive pressure and negative draft applications.

○ Adjustable Sensor Dampening to reduce the effects of flame induced draft pulsations.

○ Adjustable Proportional Band for control of the rate of actuator movement in relation to the set point.

○ Adjustable Dead Band to prevent actuator “hunting” near the set point.