In-Situ Oxygen Sensor

Preferred Instruments engineers and manufactures boiler control systems for commercial, industrial, and institutional facilities. The Model ZP, In-Situ Oxygen Sensor, provides reliable long life flue gas oxygen measurements.

  • Reliable, Long Life Flue Gas Oxygen Measurement
  • Separate Field Mounted Transmitter Not Required
  • Simple Automated Calibration
  • Integral Oxygen Trim and Boiler Efficiency Control Logic
  • Instrument Air Is Not Required
  • Overview and Features
  • Application
  • Specifications
  • Documents
Overview and Features

Preferred Instruments engineers and manufactures boiler control systems for commercial, industrial, and institutional facilities. Preferred’s boiler control systems include combustion, feedwater (drum level), draft & flue gas recirculation control functions. Preferred’s integrated control systems provide a full scope control package that assures safe and efficient control with undivided system integration responsibility.

Detector: The detector consists of a zirconium oxide cell, a ceramic heater with thermocouple, terminals for connecting to the controller unit, a flange for connection to the probe, opening to accept reference (ambient) air and a connection for calibration gas. The detector works on a principle that when heated to 800° C (1472° F), the cell generates an electrical signal directly related to the Oxygen concentration of the flue gas. Flue gases are passed through a filter to prevent dust and dirt from contaminating the cell. Calibration gas can be injected into the space behind the ceramic filter to allow on-line calibration without removal from the stack.

Probe: The probe is a stainless steel assembly that mounts on a 3" 125 lb flange (flat face) located on the flue gas duct or stack. The probe protrudes into the flue gas stream and directs boiler flue gases from the middle third of the flue gas stream to the detector. The assembly’s design provides for the removal of the detector for service or replacement without the need for removal of the entire probe.

  • Reliable, Long Life Flue Gas Oxygen Measurement
  • Separate Field Mounted Transmitter Not Required
  • Simple Automated Calibration
  • Integral Oxygen Trim and Boiler Efficiency Control Logic
  • Instrument Air Is Not Required
Application

The Preferred ZP series zirconium oxide oxygen analyzer works in conjunction with Preferred PCC-IV and DCS-IIV loop controllers, the BurnerMate Universal boiler control system, and Flexfit.

Zirconium oxide in-situ oxygen analyzers are designed to be mounted permanently in the boiler stack. The zirconium oxide cell, when heated to 800 deg. C, produces a mV signal proportional to measured oxygen on a wet basis. The Preferred controller provides all probe control functions including temperature monitoring, cell temperature maintenance, monitoring, and calibration. This system is much more reliable than extractive sampling (EGA) systems that are sensitive to moisture, and rely on chemical cells that are designed to deteriorate with time and usage.

 

The Preferred ZP probe can be applied as simply an oxygen analyzer when combined with a pre-programmed PCC-IV loop controller. It can also be used to save fuel as an oxygen trim controller when combined with Preferred LTA systems, UtilitySaver systems, BurnerMate TS systems, and the BurnerMate Universal.

Specifications

System

Gas Measured: Oxygen In Flue Gases

Sensing Method: In-Situ Field-Replaceable Zirconim Detector, and Reliable Ceramic Heater

Flue Gas Temperature: 0 to 1150° F

Measuring Range: 0 to 10% Standard, 0 to 21% Field Configurable

Accuracy: +/- 1% of Reading or 0.1% O2 (Calibration Gas Dependent)

Response Time: Initial 0.1 sec / 90% 7 sec

Power Supply: 120 VAC, 60 Hz

Power Consumption: 82 VA Total (ZP and PCC-III)

Connecting Cable: 190130. Combined Signal and Power Cable. Up to 500 ft.

Indicating Electronics

Instrument: PCC-III Controller, Up To Two Probes Per PCC-III

Oxygen Trim Options: Jackshaft, Parallel Positioning or Fully Metered Combustion Applications

Boiler Efficiency: Logic Included, Optional Flue Gas Temperature T/C Required

Oxygen Signal: 4-20 mADC, Linear, Modbus RS485. (Blockware Dependent)

Ambient: 32-130º F

Case: Weather-Proof Front Panel

Power Supply: 115 VAC, 60 Hz

Display: 4.5 Digit LED Numeric Display, 6 Status LEDs

PCC-III “Z” Option Board

Isolated Inputs:

  • Probe mV Input
  • Probe Heater Type R T/C Input 
  • Spare Type J T/C Input

Output:  Fused 120 VAC Heater Supply

Probe

Application: Natural Gas, Fuel Oils

Sample gas: 0 to 1150° F

Flanges: ANSI 125 #, 4 Bolt, 3 Inch Flange

Probe Lengths: 20, 30, 45, 65 or 90 Inch

Wetted Parts: 304 Stainless Steel, Alumina, Quartz, Zirconim, Platinum

Weight: Probe of 20 Inch Length Approx. 18 lb.

Life of Zirconia Cell: Typically 3-4 Years (1 Year Warranty)

Construction:  NEMA 12

Options: 

  • 190130 Connecting Cable, (Requires ½" Conduit Minimum)
  • EPA CEM Auto Calibration Package
Documents

In-Situ Oxygen Sensor Specification

In-Situ Oxygen Sensor Presentation

In-Situ Oxygen Sensor Instruction Manual

In-Situ Oxygen Sensor Cutsheet

 