Double Wall Day Tanks - OSP Approved
Preferred double-walled day tanks provide a local supply of distillate or diesel fuel for boilers, emergency generators, or other stationary engine-driven or oil-fired equipment. Available from 60 to 500-gallon capacities, a properly sized day tank may be selected per individual job. These Preferred day tanks are sized to fit through a 36” wide passageway. Each day tank unit includes all necessary pipe connections, manual fill port, and tank gauge, along with a variety of optional accessories.
-
Complete primary and secondary tank and instrumentation package.
-
36” interior Doorway accessible.
-
Built to U.L. 142 standards.
-
OSHPD certified. Cert # OSP-0784.
-
With its high strength and heavy-duty construction, series DT-OSP day tanks cut manufacturing time and cost while maintaining Preferred’s quality and customer service.
- Overview
- Application
- Specifications
- Documents
The Model DT-OSP Double Wall Day Tanks provide a local supply of distillate or diesel fuel for boilers, emergency generators or other stationary engine driven or oil fired equipment. Available from 60 to 500 gallon capacities, a properly sized tank may be selected per individual job. For maximum fuel capacity in a minimum space, Preferred Day Tanks are rectangular in shape. Each Day Tank unit includes all necessary pipe connections, manual fill port, and tank gauge, along with a variety of optional accessories.
- Includes Secondary Tank And Instrumentation.
- 60 to 500 gallon Capacity Range.
- UL Approved, NFPA 30 compliant, OSHPD/HCAI certified.
For mission critical applications such as emergency diesel generators and dual-fuel boilers, it is recommended that at least four hours worth of fuel is immediately available to the unit without activating transfer pumps.
Primary Tank Specifications
Mounting Base: Structural Steel Channel
Metal Thickness: 10 Gauge steel
Exterior Finish: Chemical Resistant Gray Enamel, Rust Resistant Primer
Manual Fill Port: 2" NPT
Pipe Connections: Tank Fill, Engine Fuel Return, Return Pump Port, Engine Fuel Supply, Plugged Drain.
Vent Connections: Top Mounted; 2", all sizes
Emergency Vent Connections: Top Mounted; 3", 60-200 Gallon, 4", 300-500 Gallons.
Drain: Plugged 1" NPT Coupling
Approvals / Compliance: UL Approved, NFPA 30 compliant, OSHPD/HCAI certified.
Secondary Tank Specifications
Mounting Base: Structural Steel Channel
Metal Thickness: 10 Gauge steel
Exterior Finish: Chemical Resistant Gray Enamel Finish, Rust Resistant Primer.
Containment: 110% minimum Of Tank Capacity Standard
Leak Detector: Preferred RBS Float Switch
Vent Connections: Top Mounted; 2" all sizes
Emergency Vent Connections: Top Mounted; 3", 60-200 Gallon; 4", 300-400 Gallons; 6”, 500 Gallons
Drain: Plugged 1" NPT Coupling
Approvals / Compliance: UL Approved, NFPA 30 compliant, OSHPD/HCAI certified
Optional Equipment
- Return pump: 8 or 20 gpm.
- Temperature probe (in Continuous Level Probe)
FSC-based control enclosure (cannot be tank mounted)
Secondary Tank Specifications
Mounting Base: Structural Steel Channel
Metal Thickness: 10 Gauge steel
Exterior Finish: Chemical Resistant Gray Enamel Finish, Rust Resistant Primer.
Containment: 110% minimum Of Tank Capacity Standard
Leak Detector: Preferred RBS Float Switch
Vent Connections: Top Mounted; 2" all sizes
Emergency Vent Connections: Top Mounted; 3", 60-200 Gallon; 4", 300-400 Gallons; 6”, 500 Gallons
Drain: Plugged 1" NPT Coupling
Approvals / Compliance: UL Approved, NFPA 30 compliant, OSHPD/HCAI certified