Ranger Ultra-Low NOx Combustion System

Two Designs — One Solution

The Ranger Ultra-Low NOx Combustion System is a sub-9 ppm burner platform capable of firing dual fuels. The Ranger achieves 10:1 turndown on natural gas and 8:1 turndown on oil with less than 3% oxygen.

Capacity – 4 MMBTUH – 120 MMBTUH

Fuel – Natural gas, #2 - #6 Oil, specialty fuels

NOx Levels – 9 PPM for Natural Gas

Turndown – 10:1 for Natural Gas; 8:1 for #2 oil

Recommended Boiler Type – Firetube, Flextube, Firebox, Cast Iron Sectional, Watertube

Recommended Uses – Commercial or Industrial

  • Features
  • Application
  • Documents
Features

Fuel Variety: Capable of firing natural gas, light oil, heavy oil, digester gas, ethanol, and more, the Ranger offers a wide range of fuel burning capability.

Advanced Design: Our engineers specifically designed this burner to eliminate field errors, reduce space requirements, and facilitate maintenance when needed.

Model Options:  Two models are available: Ranger RF is designed for larger capacities and allows for the fan to be placed remotely; the Ranger AF is designed for smaller applications and ease of maintenance.

High Efficiency: The Ranger incorporates VFD for control of FD fan speed, resulting in significant electrical reductions, regardless of the type of fuel burned.

Low Emissions: Natural Gas: Sub 9 ppmc NOx

Application

Specification: Single burner: firetube, firebox (cast iron sectional), watertube boilers, or HTHW generators.

Fuel: No. 2 through No. 6 fuel oil, and/or natural gas (consult factory for biomass or waste fuels).

NOx Emissions: Natural gas: less than 9 ppmc. No. 2 fuel oil: less than 90 ppmc (maximum 0.01% FBN) without FGR. No. 6 fuel oil: less than 250 ppmc (maximum 0.30% FBN) without FGR.

Burner Efficiency: Any fuel: 1.5 - 2.5% excess oxygen 50 - 100% firing rate (exclusive of “tramp” air) VFD motor control for maximum electrical efficiency of combustion air. Less than 4% excess oxygen below 50% firing rate down to 10% firing rate.

Operation: Turndown: 10:1 on gas firing; 8:1 on oil firing.

Supply Pressures: The Ranger burner accommodates a wide variety of combustion applications and fuels. Specific information relating to fuels intended to be used, as well as pressures and temperatures, must be provided.

Burner Control & Monitoring: Parallel/full metering firing rate control: any Preferred controller. Oxygen sensor: Model “ZP” In-Situ sensor, reliable zirconia oxide detector. Monitoring: SCADA/Flex remote monitoring and control system. Instruments: Standard and optional equipment available.

Additional Options: Draft control, drum level control, low fire fuel changeover, dual/redundant flame scanning, smoke opacity monitoring and alarm, atomizer post purge capability, flue gas temperature indication alarm, emergency boiler shutdown.

Documents

Ranger Specification

Ranger Presentation

Ranger Brochure

 

SUBSCRIBE TO OUR MAILING LIST