PWC Changing Modbus Address From PWC Edit
FILED UNDER: ATPS, Chief Dispatcher, JC-CD, JC-CDST, PI PWC, PU PWC, PWC Pump Set, TGEL-D5Symptom
The modbus address on a PWC can be changed from PWC Edit.
Steps to Troubleshoot
Changing Modbus Address Using PWC Edit.
- From the edit Menu select ‘Modbus Setup’.
- Click the ‘Modbus Setup’ button.
- Enter the desired modbus address in address window.
- Click ‘Done’, twice to close out ‘Modbus’ dialogs.
- Press the ‘Download’ button or select ‘Download To PWC’ from the ‘File’ menu.
- Click Continue.
- Select ‘Modbus Registers + Coils’ from the ‘Select Items To Download’ dialog all other items should be deselected.
- Click Continue & complete download.
Resolution
After the program is finished downloading you can unplug the download cable and the PWC and modbus are ready for use.